How to Troubleshoot Flowmeter Errors and Inaccurate Readings

When a flowmeter produces inconsistent or inaccurate readings, it can disrupt operations, reduce efficiency, and compromise compliance. Follow this step-by-step troubleshooting guide to identify and correct common issues across various flowmeter types.

  1. Confirm Basic Conditions

Power and Signal

  • Is the flowmeter powered and properly connected?
  • Are signal cables secure and free from damage or interference?
  • Check for proper grounding—especially for electromagnetic or ultrasonic types.

Pipe Conditions

  • Is the pipe full (especially for magmeters or ultrasonic)?
  • Are there bubbles, partially filled lines, or air pockets?
  1. Inspect Installation Setup

Flow Profile Disturbances

  • Are there elbows, valves, or pumps too close to the meter?
  • Most meters require upstream/downstream straight runs (e.g., 5–10 pipe diameters).

Orientation and Positioning

  • Is the meter mounted in the correct orientation (horizontal/vertical)?
  • Are sensors placed at the correct height and not prone to sediment buildup?

Valve Position

  • Ensure control valves are downstream of the flowmeter, not upstream.
  1. Check Process Conditions

Fluid Type and Properties

  • Is the fluid conductive enough for a magmeter (≥ 5 µS/cm)?
  • Are temperature and pressure within specified limits?

Presence of Solids or Gas

  • Entrained solids or bubbles may disrupt ultrasonic and Coriolis meters.
  • Verify filtering or degassing if needed.
  1. Verify Configuration Settings

Calibration and Scaling

  • Is the meter calibrated correctly for the pipe size and flow range?
  • Are units (GPM, LPM, m³/h) and scale factors correctly programmed?

Zero Flow Offset

  • Check for false readings at zero flow—adjust the zero setting if necessary.

Damping/Filter Settings

  • Excessive damping may cause slow response or flat readings.
  1. Electrical Noise and Interference
  • Nearby motors, VFDs, or power supplies can induce signal noise.
  • Use shielded cables, proper grounding, and separate power/data wiring paths.
  1. Perform Diagnostic Checks (If Available)

Modern meters often include built-in diagnostics for:

  • Sensor health
  • Signal strength
  • Fault codes or alerts

Review the manufacturer’s manual or software for diagnostics.

Common Signs and Likely Causes

Symptom

Possible Cause

No reading

No flow, wiring issue, or power failure

Fluctuating readings

Air bubbles, poor signal, upstream turbulence

Low or zero readings

Pipe not full, air in line, incorrect calibration

High readings

Grounding issue, cross-talk, poor zeroing

Intermittent signal

Loose cables, moisture ingress, faulty electronics

When to Call the Manufacturer

  • Repeated faults with no clear cause
  • Sensor or transmitter damage
  • Firmware or compatibility concerns
  • When in doubt about diagnostics or recalibration