Electromagnetic Flowmeter Type MAGNETOFLOW™ M2000

The amplifier type M2000 is best suited for bidirectional flow measurement of fluids with a conductivity >5 μS/cm (>20 μS/cm for demineralized water). The backlight, four-line display shows all actual flow measuring data, daily and complete information, including alarm messages.The standard amplifier has 4 programmable digital outputs, one digital input, analog output and different interfaces. Integrated system self check-up makes putting into operation and servicing easier. The back-up function enables retrieval of parameters while servicing the meter, without the need for reprogramming the device or transferring to another device.

Features

  • For all detectors
  • Accuracy : ±0,2 % of actual flow
  • Flow range : 0,03 – 12 m/s
  • DN 6 – DN 2000 ( 1/4″ – 80″)
  • Protection class IP 67
  • Interfaces ModBus®, HART ™, M-Bus, Profibus DP
  • ACS, OIML R49-1 and MID MI-001 approved
  • Integrated data logger function

Technical data

Power supply 85 – 265 VAC, 45 – 65 Hz, <20 VA or optional 9-36 VDC
Analog output 0/4 – 20 mA, <= 800 ohms, flow direction is displayed upon a separate status output
Pulse/Frequency output 2  open collector outputs 24 V active, 20 mA, or 30 V passive, 100 mA max. 10 kHz 2  Solid State Relay outputs 48 Vac, 500 mA or  open collector outputs 30 V passive, 100 mA max. 1 kHz
Status output min./max. alarm, preselection meter, flow direction, error message
Medium control separate electrode
Programming 3 keys
Interface MODBUS RTU RS232 in standard
RS485 MODBUS™, M-Bus, HART™ & Profibus-DP in option
Flow range 0,03 – 12 m/s
Accuracy >= 0,5 m/s better +/- 0,2% of actual flow
<0,5 m/s +/-1,25 mm/s of actual flow
Repeatability 0,1%
Flow direction bi-directional
Pulse lenght Programmable up to 10 s
Outputs Short circuit safe and galvanically isolated
Low flow cut off 0-10%
Display LCD, 4 lines / 20 characters, backlit, actual flow, 2 totalizers, status display
Housing Powder coated aluminium die cast
Protection class IP67
Cable insertion Power and signal cable (outputs) 3 x M20
Single cable From detector M20
Ambient temperature -20°C up to +60°C

Three detector types available

DETECTOR TYPE II FOR A GREAT VARIETY OF APPLICATIONS

Size: DN 6 to DN 2000
Nominal pressure : PN 10 to PN 100

Linear materials

Type Diameter Fluid temperature
Neoprene DN 25 to 500 0 to 80°C
Hard rubber DN 25 to 2000 0 to 80°C
PFA DN 6 to 10 -40 to +150°C
PTFE DN 15 to 600 -40 to + 150°C
Halar DN 300 to 1400 -40 to +150°C

Electrodes material : Hastelloy C (standard), Tantal, Platinum / Gold plated, Platinum / Rhodium
Flange connection DIN, ANSI, JIS, AWWA, etc
Dimension according to ISO 13359,
Empty pipe electrode as Standard,
Ground electrode in the same material than the measurement electrode
Ground ring in option
IP67 or IP68 protection in option.

DETECTOR TYPE III WITH SHORT LAY LENGTH

Size : DN 25 to DN 100,
Nominal pressure : PN 40,
Linear materiel : PTFE,
Fluid temperature : -40 to +150°C,
Electrodes material : Hastelloy, Tantal, Platinum / Gold plated or Platinum / Rhodium,
Protection class : IP65 or IP68 in option.

SANITARY DETECTOR FOR LIQUID FOOD FLOW MEASUREMENT

Size : DN 10 to DN 100,
Nominal pressure : PN40,
Linear material : PTFE,
Electrodes material : Hastelloy C (standard), Tantal, Platinum / Gold plated or Platinum / Rhodium,
Housing : stainless stell,
Lay : Tri-Clamp connection, ISO 2852 or SMS DIN 11851 connection,
Protection class : IP65 or IP68 in option.