FRENIC-MEGA(G2): FRN0008G2S-2GU
Technical Support During Business Hours:
(510) 403-7866
6:00 AM – 5:00 PM (PST)
Monday – Friday
Dial Ext. 1 – General Tech Support
Dial Ext. 2 – Parts, Repair, Warranty & Service
Customer Service:
(510) 403-7861
7:30 AM – 8:00 PM (EST)
Monday – Friday
Technical Support After Business Hours:
1-888-900-3854
24 Hour Support:
Monday – Friday
6:00 AM – 11:59 PM (PST)
Service
Specifications
- Product Series: FRENIC-MEGA (G2)
- Family Series: Fuji Drives, FRENIC Mega Series
- HP Ratings
- HND: 2
- HHD: 2
- HP Ratings
- HND: 4.7
- HHD: 4.7
- Output Rated Current, 1-Phase
- HND: 8
- HHD: 8
- Overload capability
- HND: 120% Rated Current for 1 min.
- HHD: 150% Rated Current for 1 min. & 200% Rated Current for 3 sec.
- Watt loss @ Running
- LD, 3-Phase: 80
- HD, 3-Phase: 80
- Watt loss at stop: 6.7
- DCR
- DCR PN#: n/a
DCR Watt Loss: n/a
- DCR PN#: n/a
- Inverter Efficiency(%) at rated(Hz), rated(A)
- HND Low Carrier Frequency(2KHz): 93.3593647632276
- HND High Carrier Frequency: 91.2081722522338
- HHD Low carrier frequency (2kHz): 93.3593647632276
- HHD High carrier frequency: 91.2081722522338
- Nominal Input Voltage, frequency: 230, 50/60Hz
- Input Volt Range: 200-240 (50/60Hz)
- Output Volt Range: 0 – 240V, 3-Phase
- Max Output Frequency: 0.1 – 599Hz
- Digital Input: 11
- Analog Inputs: 3
- Transistor Outputs: 4
- General Purpose Relay Output: 1
- Alarm Relay Output: 1
- Braking
- HND, Torque [%]: 1.5
- HHD, Torque [%]: 1.5
- Duty Cycle HND, %ED: 14
- Duty Cycle HHD, %ED: 14
- Braking Unit Type HND: Built-in
- Braking Unit Type HHD: Built-in
- Braking Unit QTY. HND: –
- Braking Unit QTY. HHD: –
- braking resister HND: DB2.2-2C
- braking resister HHD: DB2.2-2C
- Braking Resistor QTY. HND: 1
- Braking Resistor QTY. HHD: 1
- Enclosure
- Standard: UL Open Type (IP20/IP00), Optional UL Type 1
Cooling: Natural - Weight/Mass [lbs.(kg)]: 5.7
- Drawing Open Chassis: 0
- Dimensions H x W x D (inches): 10.24 x 5.91 x 5.71
- Standard: UL Open Type (IP20/IP00), Optional UL Type 1
- NEMA Kit
- Nema/UL Type 1: NEMA1-ST-FB1
- Drawing NEMA1: 0
- Option Cards, Communication Card
- DeviceNet: OPC-DEV
- Profibus: OPC-PDP2
- Profinet: OPT-ETM
- CC-Link: OPC-CCL
- Ethernet/IP: OPT-ETM
- Modbus TCP: OPT-ETM
- BACnet/IP: OPT-ETM
- CANOpen: OPC-COP2
- T-Link Communications Card: OPC-TL
- Multiprotocol Ethernet Interface: OPT-ETM
- Option Card, Input/Output
- PG Interface Card: OPC-PG
- PG Interface Card: OPC-PG2
- PG Interface Card: OPC-PG22
- PG Interface Card For Synchronous Motor: OPC-PMPG2
- Digital Input Interface Card: OPC-DI
- Digital Output Interface Card: OPC-DO
- Analog Input/Output Interface Card: OPC-AIO
- Analog Output Interface Card: OPC-AO
- Resistance Temperature Detector Input Interface Card: OPC-PT
- Relay Output Interface Card: OPC-RY
- Relay Output Interface Card: OPC-RY2