FRENIC-MEGA(G1): FRN450G1S-4U
Technical Support During Business Hours:
(510) 403-7866
6:00 AM – 5:00 PM (PST)
Monday – Friday
Dial Ext. 1 – General Tech Support
Dial Ext. 2 – Parts, Repair, Warranty & Service
Customer Service:
(510) 403-7861
7:30 AM – 8:00 PM (EST)
Monday – Friday
Technical Support After Business Hours:
1-888-900-3854
24 Hour Support:
Monday – Friday
6:00 AM – 11:59 PM (PST)
Service
Specifications
- Product Series: FRENIC-MEGA (G1)
- Family Series: Fuji Drives, Mega Series
- HP Ratings
- LD, 3-Phase: 450
- HD, 3-Phase: 350
- Output Volt Range: 380-480
- Output Rated Current, 3-Phase
- LD, 3-Phase: 520
- HD, 3-Phase: 415
- Amps, 1-Phase
- LD, 1-Phase: Check Instruction Book
- HD, 1-Phase: Check Instruction Book
- Overload capability
- LD, 3-Phase: 120% 1min.
- HD, 3-Phase: 150% 1min., 200% 3s
- Watt loss @ Running
- LD, 3-Phase: 5600
- HD, 3-Phase: 4350
- Watt loss at stop: 188
- DCR
- DCR PN#: DCR4-280C
- DCR Watt Loss: 270
- Inverter Efficiency at rated(Hz), rated(A)
- Low carrier frequency (2kHz): 0.99
- High carrier frequency: 0.98
- Nominal Input Voltage, frequency: 460, 50/60Hz
- Input Volt Range: 380-480, +10 to -15%
- Output Volt Range: 0 – 480V, 3-Phase
- Max output Frequency: 500 Hz
- Digital Input: 7(9)*
- Analog Inputs: 3
- Transistor outputs: 4
- General purpose relay output: 1
- Alarm relay output: 1
- Braking
- LD, Torque [%]: 7 to 12%
- HD, Torque [%]: 10 to 15%
- Duty Cycle LD, %ED: –
- Duty Cycle HD, %ED: –
- Braking Unit Type:
- Braking Unit QTY.: 1
- Built-in braking resistor: DB220-4C
- Braking Resistor QTY.: 1
- Enclosure
- Standard: IP00
- Cooling: Fan
- Weight/Mass [lbs.(kg)]: 309
(140) - Drawing Open Chassis: ROA701014
- Dimensions H x W x D (inches): 39.37 x 26.77 x 14.17
- NEMA Kit
- NEMA/UL Type 1: NEMA1-220G1-24
- Drawing NEMA1: ROA701037
- Option Cards, Communication Card
- Modbus RTU: Standard
- DeviceNet: OPC-G1-DEV
- Profibus: OPC-G1-PDP
- Profinet: OPC-PRT2
- CC-Link: OPC-G1_CCL
- Ethernet/IP: OPC-G1-ETH
- Modbus TCP: OPC-G1-ETH
- BACnet/IP: OPC-G1-ETH
- CANOpen: OPC-G1-COP
- T-Link Communications Card: OPC-G1-TL
- Multiprotocol Ethernet Interface: OPC-G1-ETH
- Option Card, Input/Output
- 115VAC I/O Card – Remote Mount: OPC-115V
- Relay Output Card: OPC-G1-RY
- Digital Input Interface Card: OPC-G1-DI
- Digital Output interface card: OPC-G1-DO
- Analog Input / Output Interface Card: OPC-G1-AIO
- PG Interface Card (5V): OPC-G1-PG2
- PG Interface Card (12V): OPC-G1-PG
- PG Synchronization Card: OPC-G1-PG22