Digital Controller
(PXH Series)
High speed and high accuracy
- High speed control: 50 ms input sampling
- Indication accuracy: 0.1%
- 5-digit display can show 0.01°C
- Accepts various input: thermocouple, RTD, voltage, or current
- 9 DIs, 9 DOs, and 2 AOs
- Variety of functions: RS-485, T-Link, math function, ramp soak, transmitter power supply, complete templates
- Shallow body and front waterproof structure
- Easy parameter setting thanks to the loader software
Ideal for process control of temperature, pressure, and flow.
Specifications
Power supply voltage | 100–240 V AC, 50/60 Hz |
---|---|
Power consumption | ≤ 20 VA (at 220 V) |
Input | Thermocouple, RTD, DC voltage/current |
Indication accuracy | ±0.1% FS |
Sampling rate | 50 ms |
Input correction | zero and span adjustment, square root extraction, filter |
Auxiliary analog input | 1 point among 1–5 V, 0–5 V, 0–10 V For motor-operated valve control: potentiometer 100 Ω–10 kΩ |
Digital input | 4 points or 9 points No-voltage contact or transistor input |
Math function | Flow rate compensation with temperature and pressure, average, Max/Min selector, input switching |
Ramp soak | 64 steps, 31 patterns |
Control types | Basic, heating/cooling control, motorized valve control |
Control output | Relay contact, SSR/SSC drive, 4–20 mA DC, or motorized valve control output |
Digital output | 2 points or 9 points, SPST or SPDT |
Analog transfer output | 4–20 mA DC, up to 2 points |
Transmitter power supply | Power supply for 2-wire transmitter (17–30 V DC) |
Control method | 2-degrees-of-freedom PID with auto tuning |
Control template | Pre-installed input/output setting and calculation blocks |
Control mode | Auto, manual, or remote |
Alarm | Up to 8 points |
Alarm type | PV (high/low, absolute, deviation, zone, change rate), SV high/low, device error, hold, latch, excitation/non-excitation |
Alarm output | can be allocated to digital output |
Communication (option) | RS-485 (Modbus) |
Front keys | 4 keys (including user-defined key), with key lock function |
Display | LED, 5-digit |
Front structure | IP66, NEMA-4X equivalent |
Dimensions and weight | 96 (W) × 96 (H) × 81.5 (D) mm, approx. 500 g |
Mounting method | Panel mount |
External wiring terminals | M3 screw terminal |
Parameter loader software | Supported OS: Windows 2000, Windows XP, Windows 7 Empty hard-disk capacity: 100 MB or more Dedicated USB cable is option. Software can be used via RS-485 (Modbus) network. |
Easy parameter setting thanks to the loader software
-
Parameter upload and download is easily made by using the parameter loader software.
-
You can also check the PID tuning status on PC.
-
To use the software, connect between the loader port of PXH and PC with cable, or via RS-485 communication.